Hot Product

Product drawing»

Structural drawing»

You are here:  

2-position 3-way solenoid pilot valve for on-off service

2010-10-20

N1.What is the Limit switches used for? N2. Why does this limit switch on the on-off valve not provide any alarm in the control room? N3. Our are ask for deciding these pneumatic hand switch remote open/close from DCS is necessary or not. The P&ID depicts position switch contacts wired to the DCS. The I could include some interlock logic in addition to the status display. This example does not appear to include automatic valve actuation, only operator initiated remote activation. BTW, I prefer the term position switch for contacts that provide open or closed position status. The term limit switch is often used on electric motor operated valves describing contacts that stop the motor when the valve is at full open or travel. The open or closed status of a valve is not necessarily and alarm situation. This appears to be operator initiated activity to open or close the valve. Hwoever the open status could be used as an interlock to permit starting a pump, etc. N3. Our (process engineers) are ask for deciding these pneumatic hand switch (*HS A/B in the attached drawing) remote open/close from DCS is necessary or not. The operating philosophy or project engineering standards might define when valves should be remotely operated. However the P&ID reflects the automated valve actuator. With the hardware provided it makes sense to permit the operator to open and close remotely. Often the valve pneumatic components include a selector to permit opening or closing at the valve. This scheme suggests a double acting valve, no spring or failure position. A volume bottle could provide stored energy to operate when the air supply fails. The de-energized direction on the solenoid valve suggests that this is a spring operated valve. The failure position of the valve is not shown. If a blowdown valve different clients have different requirements. Fail closed is normal for an isolation or shutdown valve. If it is an emergency shutdown valve a selector could be for automatic or close instead of open or close. This could prevent isolating the automatic control.

MORE NEWS

  • Two stage DX cooling coil
  • Inrush current solenoid valve
  • ESD Valve actuator
  • Simple gravity question
  • Shanghai MeiYan Yi Pump & Valve Co., Ltd.
    MeiYan Yi solenoid valve Contact MeiYan Yi
    Shanghai Enine Pump & Valve Co., Ltd.
    Enine solenoid valve Contact Enine
    Shanghai Saitai Pump & Valve CO., Lid.
    Saitai solenoid valve Contact Saitai
    Shanghai Fengqi Industrial Development Co., Ltd.
    FengQi solenoid valve Contact FengQi